Dual Voltage
(Run and start winding) Capacitors in start windings are rated for lower voltage. |
 |
| VOLTAGE | ROTATION | L1 | L2 | JOIN |
| HIGH | CCW | 1,8 | 4,5 | 2,3,6,7 |
CW | 1,5 | 4,8 | 2,3,6,7 |
| LOW | CCW | 1,3,6,8 | 2,4,5,7 | --- |
CW | 1,3,5,7 | 2,4,6,8 | --- |
|
|
| NEMA NOMENCLATURE - SINGLE PHASE - DUAL VOLTAGE |
|
|
|
|
|